Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR02385

Parcel: 12612244D


Addresses:

4545 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - ADMINISTRATION

Plan Number - T08FR02385

Inspection Description - VIOL - ADMINISTRATION

Inspection Status - Approved

Date Description Inspector Results Comments
08/12/2008 VIOL - ADMINISTRATION Approved petition of appeal to the Fire Chief on 07/16/08. - to eliminate two of the exterior exit doors that service the warehouse area of their store.

APPROVED WITH STIPULATIONS on 08/12/2008. To block the non-required exit doors.

The non-required exit doors shall be covered so they are no longer recognizable as exits from the egress side. Provide an exit sign from the area directing occupants to the nearest exit.

A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.

The signs shall be in place by August 28, 2008.

Per Chief Dan Uthe.