Case: T08FR02375

Parcel: 129020870


Addresses:

2744 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
10/13/2008 VIOL - FIRE PROTECTION SYSTEMS Approved
08/12/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11 Hood filters must be cleaned and maintained free of grease.
08/12/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11 Install a sheet metal separator 8" above the deep fryer, to separate from open flame equipment.
08/12/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11 Deep fryer must be completely under hood system.
08/12/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 906.1 BC or K-type extinguishers (2) must be "installed" in kitchen; w/in 30' of cooking line.
08/12/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11 Install signage 'Emergency Pull Handle" w/ an arrow visible from cooking line.