Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR02375
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2008 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
08/12/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11 Hood filters must be cleaned and maintained free of grease. | |
08/12/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11 Install a sheet metal separator 8" above the deep fryer, to separate from open flame equipment. | |
08/12/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11 Deep fryer must be completely under hood system. | |
08/12/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.1 BC or K-type extinguishers (2) must be "installed" in kitchen; w/in 30' of cooking line. | |
08/12/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11 Install signage 'Emergency Pull Handle" w/ an arrow visible from cooking line. |