Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 10/13/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Approved |
|
| 08/12/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 904.11 Hood filters must be cleaned and maintained free of grease. |
| 08/12/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 904.11 Install a sheet metal separator 8" above the deep fryer, to separate from open flame equipment. |
| 08/12/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 904.11 Deep fryer must be completely under hood system. |
| 08/12/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 906.1 BC or K-type extinguishers (2) must be "installed" in kitchen; w/in 30' of cooking line. |
| 08/12/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 904.11 Install signage 'Emergency Pull Handle" w/ an arrow visible from cooking line. |