Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR02370
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.08/26/08 | |
| 08/11/2008 | INSP - FULL | Violation | 1.) TFC 315.2.1 STORAGE IN SPRINKLERED BUILDINGS MUST BE MAINTAINED 18'' BELOW THE SPRINKLER HEAD DEFLECTOR. THE TIRE STORAGE MUST BE LOWERED TO MAINTAIN REQUIRED CLEARANCE BELOW SPRINKLER HEAD. | |
| 08/11/2008 | INSP - FULL | Violation | 2.) TFC 605.4 THE MULTI-PLUG ADAPTER ON THE EAST WALL OF THE GARAGE AREA USED TO POWER PORTABLE LAMPS NEEDS TO BE REPLACED WITH AN APPROVED UL LISTED POWER STRIP WITH OVERCURRENT PROTECTION. |