Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR02345
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. _____ Move your cooking device I.E. burners, fryer, grill to correctly line up with the hood systems's extinguishing nozzles _____ Correct the hood filters in order to avoid any open spaces and to ensure that filtering system is working properly. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ The Hood extinguishing system shall be serviced or the proper paper work shall be provided to show proof that the system meets code standards _____ The automatic sprinkler system shall be serviced or the proper paper work shall be provided to show proof that the system meets code standards _____ A sprinkler head shall be dropped into the beer cooler located on the west side of the building to comply with required sprinkler coverage for the building 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ The hood system in your building has been found unfit and requires a cleaning. You are to have your hood system cleaned immediately and provide the proper paper work to prove that the required cleaning has been done professionally. |