Case: T08FR02335

Parcel: 133291790


Addresses:

8467 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
12/08/2008 VIOL - FIRE PROTECTION SYSTEMS Approved The pre-action system has been removed and the area covered by the facilities wet pipe sprinkler system. CLOSED!
08/08/2008 VIOL - FIRE PROTECTION SYSTEMS Approved 01. The PRE-ACTION Fire Suppression System is not in service. Have system repaired or converted to a wet pipe system and connected to the current system in the facility. INTERNATIONAL FIRE CODE (IFC) 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.