Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 12/08/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Approved |
The pre-action system has been removed and the area covered by the facilities wet pipe sprinkler system. CLOSED! |
| 08/08/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Approved |
01. The PRE-ACTION Fire Suppression System is not in service. Have system repaired or converted to a wet pipe system and connected to the current system in the facility. INTERNATIONAL FIRE CODE (IFC) 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. |