Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - ADMINISTRATION
Plan Number - T08FR02328
Inspection Description - VIOL - ADMINISTRATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2008 | VIOL - ADMINISTRATION | Approved | petition of appeal to the Fire Chief on 12/20/07. -Sears would like to convert one of their required exits to an emergency exit only. APPROVED WITH STIPULATIONS on 12/28/07. - 1. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system. 2. The doors unlock upon loss of power controlling the lock or lock mechanism. 3. The door locks or lock mechanisms shall have the capability of being unlocked by a signal from the fire command center. 4. The initiation of an irreversible process which will release the latch in not more than 15 seconds when a force of not more than 15 pounds is applied for 1 second to the release device. Initiation of the irreversible process shall activate an audible signal in the vicinity of the door. Once the door lock has been released by the application of force to the releasing device, relocking shall be by manual means only. 5. A sign shall be provided on the door located above and within 12 inches of the release device reading: PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS. 6. Emergency lighting shall be provided at the door. per Chief Dan Uthe. |