Case: T08FR02311

Parcel: 12002043A


Addresses:

761 W AJO WY

Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
09/24/2008 VIOL - MOTOR FUEL DISPENSING Approved Approved.
08/06/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

· Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
08/06/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

· Please provide documentation that the shear valves are checked