Inspection History: VIOL - MOTOR FUEL DISPENSING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2008 | VIOL - MOTOR FUEL DISPENSING | Approved | Approved. | |
| 08/06/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. · Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer. |
|
| 08/06/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage. · Please provide documentation that the shear valves are checked |