Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR02231
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2008 | INSP - FULL | Approved | All violations were corrected and application for new C of O has been submitted. | |
09/04/2008 | INSP - FULL | Correction Required | Moving foward! The patio now has an exit gate with panic hardware. They still need to have the hood cleaned from filters to vents on roof. Extinguishers still need to be inspected and mounted. Occupant load will be posted pending C of O. Still waiting for fire approval for a C of O. | |
08/01/2008 | INSP - FULL | Violation | 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. Clean up the combustible storage behind your refridgerator, on top of the refrigderator, in closet in office area ( blocking electrical panel), and near the hot water heater in the kitchen. | |
08/01/2008 | INSP - FULL | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Clear a space around your electrical panels in office and kitchen area. | |
08/01/2008 | INSP - FULL | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove your extension cords behind bar, 2 on the patio, and anywhere else in use on the premises. | |
08/01/2008 | INSP - FULL | Violation | 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. Replace the cube adapter that is above the "waitress drink printer" and behind the bar with an approved power strip with oversurge protection. | |
08/01/2008 | INSP - FULL | Violation | 1028.4 Exit signs. Exit signs shall maintained in accordance with Section 1011 of the 2006 IFC. Cause your exit signs to light. | |
08/01/2008 | INSP - FULL | Violation | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. You will have your K-class extinguisher mounted within 30 feet of your deep fat fryers. | |
08/01/2008 | INSP - FULL | No Violation | 906.2 General requirements. Portable fire extinguishers shall be maintained in accordance with this section and NFPA 10. Your extinguisher is due to be serviced this month; it is not in violation yet. Have your K class extinguisher serviced by a qualified company or individual before the reinspection. | |
08/01/2008 | INSP - FULL | Violation | 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. Your filters have a build up of grease. Have your hood system cleaned from filters to vent in roof and provide paperwork of such. |
|
08/01/2008 | INSP - FULL | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Replace cover on electric panel in kitchen, on wall switch in office, outlet in office, a cover plate over open junction box in office, the cover over the circuitry in your deepfat fryer in kitchen, and anywhere else their is an open electrical box. | |
08/01/2008 | INSP - FULL | Violation | 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. Provide clear exit width to rear kitchen exit; remove storage rack on the left that is lessening exit width. | |
08/01/2008 | INSP - FULL | Violation | 310.7 Burning objects. Lighted matches, cigarettes, cigars or other burning object shall not be discarded in such a manner that could cause ignition of other combustible material. Cigarettes shall not be thrown over patio fence where they can ignite brush or other combustibles. | |
08/01/2008 | INSP - FULL | Violation | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Secure your CO2 cylinders, behind the bar and near the rear kitchen exit, to a sturdy object to prevent falls. |
|
08/01/2008 | INSP - FULL | Violation | 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. You will post your occupant load in a conspicuous place in the bar area near the main exit. |