Case: T08FR02202

Parcel: 12001001J


Addresses:

1285 W AJO WY


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T08FR02202

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2008 VIOL - MOTOR FUEL DISPENSING Approved All abated.
07/30/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

· Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
07/30/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times.

· Replace all cracked and damaged hoses
- Hose #4- leaking, check fittings.
- Hose #5- Replace.