Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR02193

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: INSP - SELF INSPECTION PROGRAM

Case Number - T08FR02193

Inspection Description - INSP - SELF INSPECTION PROGRAM

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2008 INSP - SELF INSPECTION PROGRAM Approved Re-inspection performed today revealed all idscrepancies corrected. CLOSED!
07/29/2008 INSP - SELF INSPECTION PROGRAM Approved 01. Fire extinguishers require an annual inspection / servicing. National Fire Protection Association Standard 10.7.1.2.1. A trained and certified person who has undergone the instructions necessary to reliably perform maintenance and has the manufacturer's service manual shall service the fire extinguishers not more than 1 year apart.
02. The main exit door has a double-key locking device which requires a sign posted saying "THIS DOOR TO REMAINUNLOCKED
WHEN BUILDING IS OCCUPIED". The sign shall be in letters 1inch (25 mm). Post a sign. INTERNATIONAL FIRE CODE (IFC) 1008.1.8.3.
03. Exit lights/signs are not illuminated. Illuminate the signs. IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator.
22 AUGUST 08 SUSPENSE.