| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2008 | INSP - FULL | Approved | approved | |
| 07/25/2008 | INSP - FULL | Correction Required | 1) THE LIGHT FIXTURE IN THE ROOF HATCH ROOM SHALL BE HARD WIRED 2) ALL STORAGE SHALL BE A MINIMUM OF 18 INCHES BELOW A SPRINKLER DEFLECTOR 3) EXTENTION CORDS SHALL NOT BE USED AS PERMANENT WIRING 4) REPAIR THE LIGHT FIXTURE IN THE OLD CARPER SAMPLE ROOM 5) STORAGE SHALL BE 36 INCHES FROM ELECTRICAL PANELS 6) TEST AND REPAIR AS NECESSARY ALL EMERGENCY LIGHTING 7) REMOVE ALL WIRING, ETC. FROM SPRINKLER PIPING |