Case: T08FR02137

Parcel: 13615018A

Inspection Status: Approved

Inspection History: COMPL - REINSPECTION

Date Description Inspector Results Comments
07/24/2008 COMPL - REINSPECTION Approved The commercial cooking supression system was inspected and tested, the burner and fryer were moved back to area they were designed to be in, and coverage is now adequate. The K extinguisher has been serviced.
07/23/2008 COMPL - REINSPECTION Correction Required The commercial cooking supression system has not been serviced/ inspected since Feb of 07 when they had a fire. The burners are moved and nozzles do not provide correct coverage for burner and fryer. Type K extinguisher in not mounted on wall and has not been serviced in over a years time. Given 24 hrs to comply or shut down cooking processes.