Case: T08FR02135

Parcel: 136406740


Addresses:

9610 E 22ND ST


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T08FR02135

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/08/2008 INSP - FULL Correction Required Sprinkler system has not been tested since
07/24/2008 INSP - FULL Violation IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
07/24/2008 INSP - FULL Violation IFC 907.20.1 Maintenance required. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection or any other feature is required for compliance with the provisions of this code, such device, equipment, system, condition, arrangement, level of protection or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as
directed by the fire code official.

907.20.5 Maintenance, inspection and testing. The building owner shall be responsible for ensuring that the fire and life safety systems are maintained in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for maintaining, inspecting and testing such systems. A written record shall be maintained and shall be made available to the fire code official.

You shall have your fire alarm system serviced and brought back into working order.
07/24/2008 INSP - FULL Violation IFC 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
You will have your fire extinguisher inspected by a qualified company or individual.