Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2008 | VIOL - FLAMMABLE LIQUIDS | Approved | ||
| 07/24/2008 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. - Install normally closed vents or the vent outlets shall discharge outside of the building. |
|
| 07/21/2008 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. - Emergency venting shall be installed on both tanks. |