Case: T08FR02109

Parcel: 11108148B


Addresses:

3575 E GRANT RD

Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE LIQUIDS

Date Description Inspector Results Comments
09/08/2008 VIOL - FLAMMABLE LIQUIDS Approved
07/24/2008 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
- Install normally closed vents or the vent outlets shall discharge outside of the building.
07/21/2008 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires.
- Emergency venting shall be installed on both tanks.