Case: T08FR02097

Parcel: 129041280


Addresses:

1935 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T08FR02097

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2008 INSP - AST/UST Approved Vents are installed. permit issued
07/23/2008 INSP - AST/UST Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30

ยท All tanks must have emergency vents installed that meet the requirements set by the tank manufacturer. All other openings shall be sealed when not in use.