Inspection History Details
Inspection Status: Approved
Inspection History: INSP - AST/UST
Case Number - T08FR02097
Inspection Description - INSP - AST/UST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2008 | INSP - AST/UST | Approved | Vents are installed. permit issued | |
07/23/2008 | INSP - AST/UST | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30 ยท All tanks must have emergency vents installed that meet the requirements set by the tank manufacturer. All other openings shall be sealed when not in use. |