Case: T08FR02077

Parcel: 13615018A

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/22/2008 INSP - FULL Violation IFC 315.2 Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. You will remove all combustibles within a a 12 inch radius of the pilot light on your hot water heater.
07/22/2008 INSP - FULL Violation IFC 605.1 Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. You are hereby ordered to IMMEDIATELY STOP use of your outdoor sign until the power supply to it is inspected and approved by a certified electrical inspector and is in compliance with Internation Electrical Code requirements.
07/22/2008 INSP - FULL Violation IFC 605.3 A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. You will maintain these distances in front of your electrical panel.
07/22/2008 INSP - FULL Violation IFC 605.5 Extension cords and flexible cords shall not be a substitute for permanent wiring. You will stop remove the 2 extension cords being used for the outdoor sign and 1 for the microwave in the kitchen, and anywhere else in use.
07/22/2008 INSP - FULL Violation IFC 605.6 Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. You will have removed the open wiring splice from your outlet located on the SE corner ceiling of the dining area. You will have a cover placed over your open junction box in the front eaves of the shop.
07/22/2008 INSP - FULL Violation IFC 1028.4 Exit signs shall be installed and maintained in accordance with Section 1011 of the 2006 IFC.
1011.1 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel.
You will have the exit sign in your kitchen repaired in an appropriate manner - to read EXIT.
07/22/2008 INSP - FULL Violation IFC 605.9 Temporary wiring methods shall meet the applicable provisions of the ICC Electrical Code. You will stop remove the 2 extension cords being used for the outdoor sign. You will have removed the open wiring splice from your outlet located on the SE corner ceiling of the dining area.
07/22/2008 INSP - FULL Violation IFC 605.5.1 Where extension cords can be used they shall be plugged directly into an approved receptacle. You will have removed the open wiring splice from your outlet located on the SE corner ceiling of the dining area.
07/22/2008 INSP - FULL Violation IFC 1028.3 A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice. Remove objects blocking full range of motion of your exit door in the kitchen.
07/22/2008 INSP - FULL Violation IFC 906.5 Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use.
906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view.
Place your extinguishers in plain view for employees, and keep them unobstructed from use.
07/22/2008 INSP - FULL Violation IFC 906.7 Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. You will have your extinguishers mounted in an approved method.
07/22/2008 INSP - FULL Violation IFC 904.11.6.4 Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. You will have your hood and commerciall cooking extinguishing system inspected and tested by a qualified company/individual and provide paperwork of such.
07/22/2008 INSP - FULL Violation IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. You will have your hood system cleaned by a qualified company or individual.