Case: T08FR02063

Parcel: 134251910


Addresses:

1060 S KOLB RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/13/2008 INSP - FULL Approved
07/22/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: No class K portable fire extinguisher (Silver). A class K fire extinguisher is required in conjunction with a wet automatic hood fire suppression system.
TFC REFERENCE: 904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be
provided within a 30-foot (9144 mm) travel distance of
commercial-type cooking equipment. Cooking equipment
involving vegetable or animal oils and fats shall be protected
by a Class K rated portable extinguisher.
REQUIRED CORRECTION: Provide a class K portable fire extinguisher within 30 feet of fryer.

___2. PROBLEM: Current extinguisher is not rated for cooking equipment and is on the floor. When you obtain the class K portable fire extinguisher you must have it mounted on a bracket.
TFC REFERENCE: 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be
securely anchored to the mounting surface in accordance with
the manufacturer’s installation instructions.
REQUIRED CORRECTION: Have class K portable fire extinguisher mounted on a bracket.

___3. PROBLEM: Hood system service records not readily available on premises for inspection.
TFC REFERENCE: 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
TFC REFERENCE: 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
REQUIRED CORRECTION: Keep a folder on the premises with copies of any and all service records (3 years worth) for ready inspection by fire code official.

___4. PROBLEM: Unapproved extension cord in use in back room.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. REQUIRED CORRECTION: Use approved power strip with GFI.

___5. PROBLEM: Power strip plugged into extension cord.
TFC REFERENCE: 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
REQUIRED CORRECTION: Plug power strip directly into electrical outlet.

___6. PROBLEM: Unsecured tanks of compressed gas in back room.
TFC REFERENCE: 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.
REQUIRED CORRECTION: Secure compressed gas cylinders from falling over.

___7. PROBLEM: Barrel out near dumpster has no label on it identifying it's contents.
TFC REFERENCE: 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an
approved manner.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

__X_Approved

___Not Approved