Case: T08FR02033

Parcel: 10321671B

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02033

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/17/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.4 Power source. Where emergency illumination is
required in Section 1027.5, exit signs shall be visible under
emergency illumination conditions.

_____1. The exit sign located above the west exit door shall have emergency back-up power.
07/17/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:

2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background.

_____1. Post the above stated sign on the inside of the west exit door.
07/17/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.



_____1. Repair or replace the emergency lighting unit located on the wall South of the fryers.

_____2. Repair or replace the emergency lighting unit located by the East exit door.




________________________________________________
(John E. Bieg, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

______________________________
(Captain)

Full inspection done by Inspector John E. Bieg
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg