Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MOTOR FUEL DISPENSING
Case Number - T08FR01970
Inspection Description - VIOL - MOTOR FUEL DISPENSING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2008 | VIOL - MOTOR FUEL DISPENSING | Approved | ALL O.K., Paperwork recieved. | |
07/17/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. · Please provide documentation of test results |
|
07/17/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times. · Replace all cracked and damaged hoses |