Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/30/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/30/08 |
| 07/16/2008 |
INSP - FULL |
|
Violation |
1.) TFC 508.5.4 REMOVE STOCK TO MAINTAIN 3 FEET OF CLEARANCE AROUND SPRINKLER RISER AND FIRE ALARM CONTROL PANEL IN SOUTHWEST CORNER OF STOCKROOM. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
2.) TFC 605.3 REMOVE STOCK TO MAINTAIN 30" WORKING SPACE IN FRONT OF ELECTRICAL PANELS IN SOUTHWEST CORNER OF STOCKROOM. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
3.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER ON EAST WALL OF STOCKROOM NEAR THE ROOF ACCESS LADDER IS PAST DUE FOR ANNUAL INSPECTION. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
4.) TFC 906.2 REMOVE STOCK TO PROVIDE READY ACCESS TO PORTABLE EXTINGUISHER MOUNTED ON EAST WALL OF STOCKROOM. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
5.) TFC 605.3 REMOVE STOCK TO PROVIDE A 30" WORKING SPACE IN FRONT OF ELECTRICAL PANEL ON EAST WALL OF STOCKROOM. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
6.) TFC 325.2.1 RE-ARRANGE STORAGE IN PHARMACY STORAGE ROOM TO MAINTAIN 18" CLEARANCE FROM THE SPRINKLER HEAD. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
7.) TFC 605.1 THE EXTENSION CORDS RUNNING ABOVE THE CEILING TILE ON AISLE 7 MUST BE REMOVED. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
8.) TFC 605.6 ELECTRICAL OUTLET BENEATH COMPUTER IN THE PHARMACY NEEDS TO HAVE A COVER PLATE INSTALLED. |
| 07/16/2008 |
INSP - FULL |
|
Violation |
9.) TFC 605.5 THE EXTENSION CORD BEHIND THE PHOTO PRINTER NEEDS TO BE REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION. |