Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR01961
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2008 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Approved in permits plus on 12/09/09 by L. Lakey. Passed test. | |
07/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 904.11.6.5 Fusible links and sprinkler heads shall be replaced annually. You will have a certified and qualified individual or company replace your fusible links in your commercial cooking extinguishing system. | |
07/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 904.11.4.1 Sprinklers shall be listed for that application and installed in accordance with their listing. You will have your nozzles replaced with UL listed nozzles and in accordance to their application by a qualified company or individual. | |
07/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 904.11 Preengineered wet chemical extinguishing systems shall be tested in accordance with the UL 300. You will have your system hydrostatically tested by a qualified individual or company. |