Case: T08FR01961

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR01961

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2008 VIOL - FIRE PROTECTION SYSTEMS Approved Approved in permits plus on 12/09/09 by L. Lakey. Passed test.
07/16/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.6.5 Fusible links and sprinkler heads shall be replaced annually. You will have a certified and qualified individual or company replace your fusible links in your commercial cooking extinguishing system.
07/16/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.4.1 Sprinklers shall be listed for that application and installed in accordance with their listing. You will have your nozzles replaced with UL listed nozzles and in accordance to their application by a qualified company or individual.
07/16/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11 Preengineered wet chemical extinguishing systems shall be tested in accordance with the UL 300. You will have your system hydrostatically tested by a qualified individual or company.