Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T08FR01957
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2008 | INSP - FULL | Violation | Currently kitchen hood extinguishing system is not in compliance with fire code requirements. This is indicated by the semi annual hood system report and a non-compliance tag or lack of compliance tags on manual activation devices. The fire code requires: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. Please ensure current certificate or tags are affixed to manual activation devices by 8-6-08 |
|
07/16/2008 | INSP - FULL | Correction Required | Non-compliance tag of system. 12-year hydro test is due. Reports from United Fire are attached. |