Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR01955
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 8/6/08: Reinspection. Spoke with maintenance manager. He states Mechanical is scheduled to inspect Hood System. He also states that Cintas is scheduled to convert system into UL300 system in the next few weeks. Inspector Springer to F/U. | |
07/17/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Spoke with Reuben from Cintas. He will be working with the kitchen manager to convert there system to the UL 300 system. | |
07/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | The Tucson Fire Department has conducted a hood suppression system inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___ PROBLEM: Hood system is older dry chem. system and does not comply with UL 300 standard. Is currently due for hydrostatic test. Will need to convert to UL 300 system. TFC REFERENCE: 904.11 Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry- and wet-chemical extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated. Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. ___Approved ___Not Approved |