Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01941
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/29/08 | |
07/15/2008 | INSP - FULL | Violation | 1.) TFC 901.6.2 THE SPRINKLER SYSTEM MUST BE INSPECTED ANNUALLY. RECORDS OF ALL AYSTEM INNSPECTIONS, TESTS AND MAINTENANCE SHALL BE MAINTAINED OF THE PREMISES FOR A MIN. OF 3 YEARS. SHOW PROOF THAT THE SPRINKLER SYSTEM HAS BEEN INSPECTED OR HAVE IT INSPECTED. | |
07/15/2008 | INSP - FULL | Violation | 2.) TFC 904.5.1 COMMERCIAL HOOD EXTINGUISHING SYSTEMS MUST BE INSPECTED EVERY 6 MONTHS. THE KITCHEN HOOD EXTINGUISHING SYSTEM IS PAST DUE FOR INSPECTION. | |
07/15/2008 | INSP - FULL | Violation | 3.) TFC 904.5.1 THE COMMERCIAL HOOD EXTINGUISHING SYSTEM FOR THE TEPPANYAKI TABLES IS PAST DUE FOR THE 6 MONTH INSPECTION. | |
07/15/2008 | INSP - FULL | Violation | 4.) TFC 904.11.6.3 THE COMMERCIAL HOOD GREASE REMOVAL SYSTEM HAS A BUILD UP OF GREASE AND MUST BE CLEANED AS OFTEN AS NECESSARY TO PREVENT THE BUILD UP OF GREASE. HAVE THE HOOD SYSTEM CLEANED ALL THE WAY UP TO THE ROOF. | |
07/15/2008 | INSP - FULL | Violation | 5.) TFC 906.2 THE WET CHEMICAL PORTABLE EXTINGUISHER IS PAST DUE FOR THE ANNAUL INSPECTION. HAVE THE EXTINGUISHER INSPECTED. | |
07/15/2008 | INSP - FULL | Violation | 6.) TFC 605.5 THE EXTENSION CORD FOR THE COFFEE POT AND THE EXTENSION CORD FOR THE POWER STRIP MUST BE REMOVED. REPLACE WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION. | |
07/15/2008 | INSP - FULL | Violation | 7.) TFC 3003.5.3 THE CO2 BOTTLE BEHIND THE FRONT COUNTER NEEDS TO BE SECURED TO PREVENT FALLING. | |
07/15/2008 | INSP - FULL | Violation | 8.) TFC 605.4 THE ELECTRICAL MULTI-PLUG ADAPTER BELOW THE LIQUOR SHELF NEEDS TO BE REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION. | |
07/15/2008 | INSP - FULL | Violation | 9/) TFC 1003.6 THE CRATES STORED NEAR THE REAR EXIT DOOR MUST BE REMOVED TO PREVENT OBSTRUCTING THE EGRESS PATHWAY TO THE DOOR. |