Case: T08FR01909

Parcel: 10321346A


Addresses:

2180 W GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR01909

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/15/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system

_____1. Test all exit signs and emergency lighting units for emergency back-up power. Repair or replace any defective units.
Provide documentation of such work.
07/15/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency when the areas served by such exits are occupied.
Security devices affecting means of egress shall be subject
to approval of the fire code official.

_____1. Remove the storage from obstructing the exit door located in the stock room.