Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.08/05/08 |
| 07/15/2008 |
INSP - FULL |
|
Violation |
1.) TFC 605.4 TWO SMALL MULTI-PLUG ADAPTERS ABOVE DISPLAY CASE NEAR THE FRONT DOOR NEED TO REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
2.) TFC 605.6 MULTIPLE ELECTRICAL JUNCTION BOXES LOCATED BEHIND THE DISPLAY COUNTER ON THE WEST WALL NEAR THE FLOOR NEED TO HAVE COVER PLATES INSTALLED. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
3.) TFC 3003.5.3 THE HELIUM TANK ON THE WEST WALL NEEDS TO BE SECURED TO PREVENT FALLING. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
4.) TFC 703.1.1 THE CEILING TILES ABOVE THE LUNCH BREAK AREA NEED TO BE REPLACED TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
5.) TFC 605.6 ELECTRICAL JUNCTION BOX AND LIGHT SWITCH IN BUY ROOM NEED TO HAVE A COVER PLATE INSTALLED. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
6.) TFC 605.6 ELECTRICAL JUNCTION BOX IN THE SOUTHWEST CORNER OF THE UPPER DECK NEEDS TO HAVE A COVER PLATE INSTALLED. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
7.) TFC 605.6 THE LIGHT BULB SOCKET ABOVE RACK E-1 NEEDS TO BE PROPERLY SECURED TO THE JUNCTION BOX. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
8.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ON THE WEST WALL BY THE SALES COUNTER NEEDS TO BE REPAIRED/SERVICED SO THAT IT WORKS PROPERLY. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
9.) TFC 703.1.1 THE CEILING TILE ABOVE THE STAIRS LEADING UP TO THE STORAGE AREA NEEDS TO REPLACED TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
10.) TFC 605.6 THE LIGHT SWITCH FOR UPSTAIRS BATHROOM NEEDS TO HAVE A COVER PLATE INSTALLED. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
11.) TFC 315.2.1 THE STORAGE ON THE RACKS UPSTAIRS NEEDS TO BE RE-ARRANGED TO MAINTAIN 2 FEET CLEARANCE FORM THE CEILING. |
| 07/15/2008 |
INSP - FULL |
|
Violation |
12.) TFC 1003.6 MISC. STORAGE AT THE BASE OF STAIRS LEADING UP TO STORAGE AREA IS BLOCKING THE PATH OF EGRESS AND MUST BE REMOVED. |
| 07/15/2008 |
INSP - FULL |
|
No Violation |
NOTE: ENSURE THAT GASOLINE FUELED EQUIPMENT IN THE BACK ROOM HAVE ALL THE GASOLINE DRAINED FROM THE FUEL TANKS. |