Case: T08FR01908

Parcel: 122010800


Addresses:

4055 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/05/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.08/05/08
07/15/2008 INSP - FULL Violation 1.) TFC 605.4 TWO SMALL MULTI-PLUG ADAPTERS ABOVE DISPLAY CASE NEAR THE FRONT DOOR NEED TO REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION.
07/15/2008 INSP - FULL Violation 2.) TFC 605.6 MULTIPLE ELECTRICAL JUNCTION BOXES LOCATED BEHIND THE DISPLAY COUNTER ON THE WEST WALL NEAR THE FLOOR NEED TO HAVE COVER PLATES INSTALLED.
07/15/2008 INSP - FULL Violation 3.) TFC 3003.5.3 THE HELIUM TANK ON THE WEST WALL NEEDS TO BE SECURED TO PREVENT FALLING.
07/15/2008 INSP - FULL Violation 4.) TFC 703.1.1 THE CEILING TILES ABOVE THE LUNCH BREAK AREA NEED TO BE REPLACED TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING.
07/15/2008 INSP - FULL Violation 5.) TFC 605.6 ELECTRICAL JUNCTION BOX AND LIGHT SWITCH IN BUY ROOM NEED TO HAVE A COVER PLATE INSTALLED.
07/15/2008 INSP - FULL Violation 6.) TFC 605.6 ELECTRICAL JUNCTION BOX IN THE SOUTHWEST CORNER OF THE UPPER DECK NEEDS TO HAVE A COVER PLATE INSTALLED.
07/15/2008 INSP - FULL Violation 7.) TFC 605.6 THE LIGHT BULB SOCKET ABOVE RACK E-1 NEEDS TO BE PROPERLY SECURED TO THE JUNCTION BOX.
07/15/2008 INSP - FULL Violation 8.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ON THE WEST WALL BY THE SALES COUNTER NEEDS TO BE REPAIRED/SERVICED SO THAT IT WORKS PROPERLY.
07/15/2008 INSP - FULL Violation 9.) TFC 703.1.1 THE CEILING TILE ABOVE THE STAIRS LEADING UP TO THE STORAGE AREA NEEDS TO REPLACED TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING.
07/15/2008 INSP - FULL Violation 10.) TFC 605.6 THE LIGHT SWITCH FOR UPSTAIRS BATHROOM NEEDS TO HAVE A COVER PLATE INSTALLED.
07/15/2008 INSP - FULL Violation 11.) TFC 315.2.1 THE STORAGE ON THE RACKS UPSTAIRS NEEDS TO BE RE-ARRANGED TO MAINTAIN 2 FEET CLEARANCE FORM THE CEILING.
07/15/2008 INSP - FULL Violation 12.) TFC 1003.6 MISC. STORAGE AT THE BASE OF STAIRS LEADING UP TO STORAGE AREA IS BLOCKING THE PATH OF EGRESS AND MUST BE REMOVED.
07/15/2008 INSP - FULL No Violation NOTE: ENSURE THAT GASOLINE FUELED EQUIPMENT IN THE BACK ROOM HAVE ALL THE GASOLINE DRAINED FROM THE FUEL TANKS.