Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01865
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2008 | INSP - FULL | Approved | ||
07/11/2008 | INSP - FULL | Compliance | 1) tHE VEGETATION AT THE SPRINKLER SYSTEM VALVE PIT SHALL BE REDUCED SO THAT THE FIRE DEPARTMENT CONNECTION IS CLEARLY VISABLE FROM THE STREET 2) SUITE # 127 - THERE ARE SPRINKLER HEADS CLOSER TOGEATHER THAN THE ALLOWABLE 6 FEET. ONE SHALL BE REMOVER OR RELOCATED 3) ALL THREE CONTROL VALVES FOR THE SPRINKLER SYSTEM SHALL BE SECURED WITH A LOCK AND CHAIN OR ELECTRONICALY SUPERVISED 4) SUITES # 235 AND # 127 - ACCORDING TO THE DECEMBER 19, 2007 REPORT OF INSPECTION BY KAZAL FIRE PROTECTION, THE CENTRAL G B SPRINKLER HEADS THAT WERE ON RECALL ARE STILL IN SERVICE. TO ALEVIATE ANY FUTURE PROBLEM OF A MALFUNCTION OF THESE ITEMS, THEY SHALL BE CHANGED OUT |