Case: T08FR01865

Parcel: 12108001B


Addresses:

1101 N WILMOT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/07/2008 INSP - FULL Approved
07/11/2008 INSP - FULL Compliance 1) tHE VEGETATION AT THE SPRINKLER SYSTEM VALVE PIT SHALL BE REDUCED SO THAT THE FIRE DEPARTMENT CONNECTION IS CLEARLY VISABLE FROM THE STREET

2) SUITE # 127 - THERE ARE SPRINKLER HEADS CLOSER TOGEATHER THAN THE ALLOWABLE 6 FEET. ONE SHALL BE REMOVER OR RELOCATED

3) ALL THREE CONTROL VALVES FOR THE SPRINKLER SYSTEM SHALL BE SECURED WITH A LOCK AND CHAIN OR ELECTRONICALY SUPERVISED

4) SUITES # 235 AND # 127 - ACCORDING TO THE DECEMBER 19, 2007 REPORT OF INSPECTION BY KAZAL FIRE PROTECTION, THE CENTRAL G B SPRINKLER HEADS THAT WERE ON RECALL ARE STILL IN SERVICE. TO ALEVIATE ANY FUTURE PROBLEM OF A MALFUNCTION OF THESE ITEMS, THEY SHALL BE CHANGED OUT