Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR01848
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The East exit sign located in the employee only area shall be illuminated. |
|
| 07/09/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. The East exit sign located in the employee only area shall have the left indicating arrow replaced. |
|
| 07/09/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed lock from the East exit door and replace it with a thumb-turn lock. |