Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01843
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.08/06/08 | |
07/09/2008 | INSP - FULL | Violation | 1.) TFC 505.1 THIS BUSINESS NEEDS TO HAVE ADDRESS NUMBERS DISPLAYED IN ACCORDANCE WITH PIMA COUNTY ADDRESSING REQUIREMENTS. | |
07/09/2008 | INSP - FULL | Violation | 2.) TFC 1008.1.8 EGRESS DOORS SHALL BE READILY OPENALBE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE. A.) THE SLIDE BOLT LATCH ON THE REAR EXIT DOOR IS NOT PERMITTED. B.) THE DOUBLE KEYED DEAD BOLT MUST BE CHANGED TO A THUMB TURN LATCH ON THE EGRESS SIDE. |
|
07/09/2008 | INSP - FULL | Violation | 3.) TFC 605.3 A WORKING SPACE OF 30" SHALL BE PROVIDED IN FRONT OF ELECTRICAL SERVICE EQUIPMENT. THERE MUST BE A 30" CLEAR WORKING SPACE IN FRONT OF THE ELECTRICAL PANEL OUTSIDE OF THE REAR EXIT DOOR. |