Case Number - T08FR01812
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2008 | INSP - FULL | Violation | Currently the fire pump is out of service, causing the required automatic sprinkler system at this building to be out of service. This sprinkler system is required under IFC903.2.10.3 (modified) that states: Section 903.2.10.3 Buildings more than two stories. An automatic sprinkler system shall be installed throughout all buildings more than two stories or with a floor level having an occupant load of 30 or more that is located 55 feet or more above the lowest level of fire department vehicle access. Exception: Open parking garages Failure to maintain this system could result in evacuation of the building. In lieu of building evacuation, the following options are available to you; 1). Rent a fire pump. 2). Rent a fire apparatus with pump (this option may require the apparatus to be staffed with approved fire personnel); 3). Fix fire pump. |
|
07/08/2008 | INSP - FULL | Violation | 7-3-08 fire pump is out of service. Fire watch started 7-8-08- fire pump still not installed. Order given to have sprinkler fully operational by 7-9-08. |