Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2008 | INSP - FULL | Approved | ||
| 07/07/2008 | INSP - FULL | Compliance | 1) MAINTAIN 3 FOOT CLEARANCE AROUND THE SPRINKLER RISER AND INSPECTORS TEST 2) HANG THE SPARE HEAD BOX AND PROVIDE THE CORRECT NUMBER OF AND CORRECT STYLE 3) PROVIDE SPRINKLER COVERAGE IN THE JANITORS CLOSET OR REMOVE CEILING 4) REMOVE THE BIRDS NEST FROM THE WATER MOTOR GONG AND ASSURE THAT IT IS WORKING |