Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE LIQUIDS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2008 | VIOL - FLAMMABLE LIQUIDS | Correction Required | TFC 3404.4.6 Clearance from combustibles. The storage area shall be kept free from weeds, debris and combustible materials not necessary to the storage. The area surrounding an exterior storage area shall be kept clear of such materials for a minimum distance of 15 feet (4572 mm). _____1. Remove all vegetation and other combustible rubbish located within 15 feet of the Diesel fuel tank and maintain this required clearance. ________________________________________________ (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after ___/___/___ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. Thank you. All noted Tucson Fire Code violations have been corrected: ____/____/____ ______________________ John E. Bieg |