Case: T08FR01802

Parcel: 103090520


Addresses:

3909 N RUNWAY DR

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
07/07/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:

2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background,

_____1. Post the above wording on the inside of the main office security grill.

_____2. Post the above wording on the inside of the West door/security grill located in the break room.

_____3. Post the above wording on the inside of the west door/security grill located in the maintenance office.
07/07/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency when the areas served by such exits are occupied.
Security devices affecting means of egress shall be subject
to approval of the fire code official.

_____1. Repair the broken restroom door located in the bollegraph area.
07/07/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1. Remove the keyed lock and locking hasp from the restroom door located in the bollegraph area.

_____2. Remove the double-keyed lock from the East door located in the maintenance office and replace it with a thumb-turn lock.

_____3. Remove the padlock and locking hasp from the scale house door
07/07/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or
surface bolts are not permitted.

_____1. Remove the surface bolt from the southwest door located in the maintenance shop and replace it with a thumb-turn lock.

_____2. Remove the surface bolt from the East door located in the maintenance shop.

_____3. Remove the surface bolt from the East door located in the break room and replace it with a thumb-turn lock.

_____4. Remove the surface bolt from the door located in the maintenance manager's office and replace it with a thumb-turn lock.