Case: T08FR01799

Parcel: 14117007P


Addresses:

7585 S HOUGHTON RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01799

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/02/2008 INSP - FULL Approved Inspection today. All items abated.
08/26/2008 INSP - FULL Correction Required Third reinspection today. Sprinkler system and 60 B:C fire extinguisher lacking service/test tags. Discussed issue with Capt. Traci as business has already been precited for these issues. Per Capt. Traci will give Chuy's until tommorrow afternoon to demonstrate that they have contacted a qualified individual to test their sprinkler system and service the fire extinguisher and mount it on a bracket. Notified manager who stated that she would make the necessary arrangements today. Will check on status tommorrow.
08/26/2008 INSP - FULL Correction Required 1400: Spoke with manager kelly who states she has made an appointment with Ideal Fire to inspect sprinkler system and fire extinguisher on 8/28/08. Contacted Independent Fire and confirmed this.
08/13/2008 INSP - FULL Correction Required Reinspection: Items number 6, 7, 9 not abated. Wrote up precite and had manager sign. Left copy. Will reinspect 8/26 and issue citation if items not abated.
07/24/2008 INSP - FULL Correction Required Reinspection today. Found items number 2,6,7,9,10 not abated. Spoke with manager. Will return 8/12 and precite if items not abated.
07/03/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Cube adapter in outlet behind bar.
TFC REFERENCE: 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
REQUIRED CORRECTION: Plug appliances directly into outlet or use GFI power strip.

___2. PROBLEM: Power strip piggy backed onto another power strip in office.
TFC REFERENCE: 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
REQUIRED CORRECTION: Power strip must be plugged directly into outlet.

___3. PROBLEM: Hood suppression system was last serviced/tested in 12/06.
TFC REFERENCE: 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system.
Inspection shall be by qualified individuals, and a certificate
of inspection shall be forwarded to the fire code official
upon completion.
REQUIRED CORRECTION: Have qualified individual service hood every 6 months.

___4. PROBLEM: Caps missing from a couple of nozzle tips on hood suppression system.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. AND NFPA 17A: NFPA 17A, 4.3.1.5: All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors, moisture or other foreign materials into the piping. REQUIRED CORRECTION: Have qualified professional replace missing tips on hood system discharge nozzles.

___5. PROBLEM: Discharge nozzle over griddle is blocked by apparently recently installed appliance. This appliance was added after installation of hood system and was not part of the originally designed system.
TFC REFERENCE: 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection
whenever the building is altered, remodeled or added to. Alterations
to fire protection systems shall be done in accordance
with applicable standards.
REQUIRED CORRECTION: Remove added appliance or present documentation from contractor stating that this is accepatble/will not affect nozzle coverage.

___6. PROBLEM: No service tag on class K fire extinguisher or 60 B:C fire extinguisher. These must be serviced yearly. TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.
REQUIRED CORRECTION: Have qualified individual service fire extinguishers.

___7. PROBLEM: Fire Sprinkler system riser lacks yearly test/service tag.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.
REQUIRED CORRECTION: Have qualified individual inspect and test sprinkler system..

___8. PROBLEM: No service records for hood system/sprinkler system available on premises for inspection.
TFC REFERENCE: 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
REQUIRED CORRECTION: Have all service records of hood system and sprinkler system available on premises for inspection by fire code official.

___9. PROBLEM: Sprinkler riser completely blocked.
TFC REFERENCE: 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould
prevent such equipment or fire hydrants from being immediately
discernible. The fire department shall not be deterred
or hindered from gaining immediate access to fire protection
equipment or fire hydrants.
REQUIRED CORRECTION: Access to sprinkler system riser and associated components shall not be blocked.

___10. Certificate of Occupancy not posted.
TFC REFERENCE: 105.3.5 Posting the permit. Issued permits shall be kept on the premises designated therein at all times and shall be
readily available for inspection by the fire code official.
REQUIRED CORRECTION: Have Certificate of Occupancy posted for inspection by fire code official.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.