Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2008 |
INSP - FULL |
|
Approved |
NOTED TFC VIOALTIONS HAVE BEEN CORRECTED. AWNING REMOVED. 11/05/08. |
| 07/03/2008 |
INSP - FULL |
|
Violation |
6.) TFC 903.2 THE COVERED PATIO DINING AREA NEEDS TO HAVE SPRINKLER HEAD COVERAGE INSTALLED BY AN APPROVED SHRINKLER SYSTEM CONTRACTOR AFTER SUBMITTING CONSTRUCTION PLANS AND OBTAINING A PERMIT. |
| 07/02/2008 |
INSP - FULL |
|
Violation |
1.) TFC 1011.4 INTERNALLY ILLUMINATED EXIT SIGNS SHAL BE ILLUMINATED AT ALL TIMES. BOTH FRONT AND REAR EXIT SIGNS NEED TO BE REPAIRED/REPLACED SO THAT THEY ILLUMINATE. |
| 07/02/2008 |
INSP - FULL |
|
Violation |
2.) TFC 605.6 THE BROKEN COVER PLATE FOR THE ELECTRICAL SWITCH NEAR THE ICE MACHINE NEEDS TO BE REPLACED. |
| 07/02/2008 |
INSP - FULL |
|
Violation |
3.) TFC 3003.5.3 THE CO2 BOTTLE OUTSIDE OF KITCHEN NEEDS TO BE SECURED TO PREVENT FALLING CAUSED BY CONTACT, VIBRATION OR SEISMIC ACTIVITY. |
| 07/02/2008 |
INSP - FULL |
|
Violation |
4.) TFC 904.11.7 DEEP FAT FRYERS SHALL BE INSTALLED WITH AT LEAST A 16 INCH SPACE BETWEEN THE FRYER AND SURFACE FLAMES OF ADJACENT COOKING APPLIANCE, OR A STEEL OR TEMPERED GLASS BAFFLE PLATE AT A MIN. 8 INCHES IN HEIGHT BETWEEN THE FRYER AND THE SURFACE FLAMES OF THE ADJACENT COOKING APPLIANCE. |
| 07/02/2008 |
INSP - FULL |
|
Violation |
5.) TFC 904.5.1 COMMERCIAL COOKING HOOD EXTINGUISHING SYSTEMS MUST BE INSPECTED EVERY 6 MO. THE HOOD SYSTEM IS PAST DUE FOR INSPECTION. |