Case: T08FR01741

Parcel: 126020220


Addresses:

999 N SWAN RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/16/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/16/08
07/01/2008 INSP - FULL Violation 1.) TFC 605.5 EXTENSION CORDS SHALL NOT BE USED FOR PERMANENT WIRING. THE EXTENSION CORD AT THE FRONT COUNTER IS NOT PERMITTED.
07/01/2008 INSP - FULL Violation 2.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER BY THE FRONT COUNTER NEEDS TO HAVE A CURRENT INSPECTION TAG.
07/01/2008 INSP - FULL Violation 3.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER LOCATED NEAR THE REAR EXIT NEEDS TO HAVE A CURRENT INSPECTION TAG.
07/01/2008 INSP - FULL Violation 4.) TFC 605.6 THE BREAKER PANEL IN THE BACK ROOM NEEDS TO HAVE BLANKS INSTALLED IN THE OPEN BREAKER SWITCH SLOTS.
07/01/2008 INSP - FULL Violation 5.) TFC 605.6 ELECTRICAL OUTLET PLATES ARE MISSING IN THE KITCHEN ABOVE THE ICE MACHINE, UNDER THE SINK AND ON THE WALL LEADING TO THE REAR EXIT.
07/01/2008 INSP - FULL Violation 6.) TFC 3003.5.3 THE CO2 BOTTLES IN THE BACK ROOM NEED TO BE SECURED TO PREVENT FALLING CAUSED BY CONTACT, VIBRATION OR SEISMIC ACTIVITY.
07/01/2008 INSP - FULL Violation 7.) TFC 904.5.1 THE COMMERCIAL HOOD EXTINGUISHING SYSTEM IS PAST DUE FOR INSPECTION. THE SYSTEM MUST BE INSPECTED BY AN APPROVED COMPANY.