Case: T08FR01733

Parcel: 141114100


Addresses:

7850 S RITA RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01733

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2008 INSP - FULL Approved
07/01/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Portable fire extinguisher in utility room is lacking a current service tag.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection,alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
REQUIRED CORRECTION: Either have portable fire extinguisher serviced or remove from premises.

___2. PROBLEM: Access to electrical panels in utility room is restricted.
TFC REFERENCE: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
REQUIRED CORRECTION: Access to electrical panels shall not be blocked.

___3. PROBLEM: Branches from tree trimmings cut and piled on property at edge of wash.
TFC REFERENCE: 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises.
REQUIRED CORRECTION: Properly dispose of branches from property. Do not burn.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved