Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01722
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOALTIONS HAVE BEEN CORRECTED.08/15/08. | |
06/27/2008 | INSP - FULL | Violation | 1.) TFC 901.6.2 SPRINKLER SYSTEM MUST BE INSPECTED ANNUALLY. RECORDS OF ALL SYSTEM INSPECTIONS, TESTS AND MAINTENANCE SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF 3 YEARS. | |
06/27/2008 | INSP - FULL | Violation | 2.) TFC 1008.1.8.3 THE MAIN EXIT DOOR NEEDS TO HAVE A VISIBLE, DURABLE SIGN ON THE EGRESS SIDE STATING " THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED". THE SIGN SHALL BE IN 1" LETTERS ON A CONTRASTING BACKGROUND. | |
06/27/2008 | INSP - FULL | Violation | 3.) TFC 1028.2 THE EMERGENCY EXIT DOOR IN THE SOUTHWEST CORNER OF THE MAIN DISPLAY FLOOR MUST BE KEPT FREE FROM OBSTRUCTIONS OR IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF A FIRE OR OTHER EMERGENCY. | |
06/27/2008 | INSP - FULL | Violation | 4.) TFC 703.1.1 THE SAGGING CEILING TILE ON THE SOUTH END OF THE BUILDING NEED TO BE SECURED INTO PLACE TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING. | |
06/27/2008 | INSP - FULL | Violation | 5.) TFC 1027.5 THE EMERGENCY ILLUMINATION UNITS NEED TO BE SERVICED OR REPAIRED SO THAT THEY OPERATE PROPERLY. | |
06/27/2008 | INSP - FULL | Violation | 6.) TFC 315.2.1 STORAGE SHELVES IN THE NORTH EAST CORNER OF THE MAIN DISPLAY AREA MUST BE RE-ARRANGED TO MAINTAIN 18" OF CLEARANCE BELOW THE SPRINKLER HEAD DEFLECTOR. | |
06/27/2008 | INSP - FULL | Violation | 7.) TFC 605.5 THE EXTENSION CORD USED TO POWER THE REFRIGERATOR MSUT BE REPLACED BY AN APPROVED, UL LISTED POWER STRIP WITH OVER CURRENT PROTECTION. | |
06/27/2008 | INSP - FULL | Violation | 8.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER IN THE WOODSHOP AREA NEEDS TO HAVE A CURRENT INSPECTION TAG. | |
06/27/2008 | INSP - FULL | Violation | 9.) TFC 605.1 THE ELECTRICAL PANELS IN THE WOODSHOP AREA NEED TO HAVE BLANKS INSTALLED TO COVER OPEN BREAKER SWITCH SLOTS. | |
06/27/2008 | INSP - FULL | Violation | 10.) TFC 605.4 THE ELECTRICAL MULTI-PLUG CUBE ADAPTER BEING USED NEAR THE TELEPHONE EQUIPMENT BOXES NEEDS TO BE REPLACED WITH AN APPROVED, UL LISTED POWER STRIP WITH OVER CURRENT PROTECTION. |