Case: T08FR01717

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01717

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
06/26/2008 INSP - FULL Violation LAUNDRY:
1.) TFC 605.3 STORAGE IS OBSTRUCTING ELECTRICAL PANELS IN LINEN HOLDING AREA AND S.E. CORNER OF PRODUCTION AREA.
06/26/2008 INSP - FULL Violation 2.) TFC 605.6 ELECTRICAL JUNCTION BOX IN N.E. CORNER OF SOILED LINEN AREA IS MISSING A COVER PLATE.
06/26/2008 INSP - FULL Violation MAINTENANCE:
1.) 605.6 IN MAINTENANCE SUPV. OFFICE (CSC) 2 ELECTRICAL JUNCTION BOXES IN CEILING HAVE COVER PLATES MISSING.
06/26/2008 INSP - FULL Violation 4.) TFC 605.6 IN MAINTENANCE SUPV. OFFICE (CSC) AN ELECTRICAL OUTLET IS MISSING THE COVER PLATE.
06/26/2008 INSP - FULL Violation CATALINA BLDG:
5.) TFC 605.4.2 IN PROPERTY MANAGER'S OFFICE A RELOCATABLE POWER STRIP IS POWERING ANOTHER POWER STRIP ("PIGGY BACKING"). EACH POWER STRIP MUST BE PLUGGED DIRECTLY INTO AN OUTLET.
06/26/2008 INSP - FULL Violation 6.) TFC 605.4 IN P.I. ANALYST'S OFFICE THE SMALL MULTI-PLUG ADAPTER UNDER THE DESK NEEDS TO BE REPLACED WITH AN APPROVED, UL LISTED POWER STRIP WITH OVER CURRENT PROTECTION.
06/26/2008 INSP - FULL Violation 7.) TFC 605.6 IN THE UP STAIRWELL AND ELECTRICAL JUNCTION BOX HAS THE COVER PLATE MISSING.