Case: T08FR01667

Parcel: 12612244D


Addresses:

4553 E BROADWAY BL

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
06/23/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cords shall not be used as permanent wiring
06/23/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Power cords at small grills shall be repaired
06/23/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Power cord for scale at front counter shall not be affixed by metal flashing of counter.
06/23/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Junction box at kitchen doorway shall have an approved cover.
06/23/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required 609.1 A commercial kitchen exhaust hood shall be installed for the range top cooking units located in the bakery kitchen.