Case: T08FR01662

Parcel: 10509546C


Addresses:

68 W RIVER RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR01662

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/23/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required 904.11.6.3 Cleaning.
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.

*** Provide the proper documentation of a regular scheduled cleaning of the hood system as they are required to be done quarterly

906.6 Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.

_____ remove any item(s) that obstruct or obscure the fire exstinguisher located in the main lobby. or place the exstinguisher in a new location where it can be seen easily.