Case: T08FR01662

Parcel: 10509546C


Addresses:

68 W RIVER RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE SERVICE FEATURES

Case Number - T08FR01662

Inspection Description - VIOL - FIRE SERVICE FEATURES

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/23/2008 VIOL - FIRE SERVICE FEATURES Correction Required 506.1 Where required.
Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.

_____ A knox box shall be required and will need to be installed in order to gain access to the building and its fire fighting features. The proper paper work shall be given and the ordering process shall begin immediatly.

510.1 Identification
Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.

_____ Place the wording "RISER ROOM" on riser room door to properly identify the fire service features location.