Case: T08FR01661

Parcel: 10509546D


Addresses:

90 W RIVER RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR01661

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/23/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

_____ Remove the secondary locking device where panic hardware exists on the rear egress door

1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

_____ Fix, repair, and bring all exit signs into code compliance

1027.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the
premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027.

_____ fix/repair and make sure all emergancy lighting unit is in working order

1028.2 Reliability.
Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied.

1028.3 Obstructions.
A means of egress shall be free from obstructions that would prevent its use.

_____ Remove any obstructions or any hinderance from the rear egress door. The door must ALWAYS be clear for exiting


________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

______________________________
(Captain)

Full inspection done by Inspector Joseph P. Longo
Re-inspection scheduled on or after ___/___/___
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.