Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Remove and/or replace the fused power strip that has sustained fire damage located in your back employee room. |