Inspection Status: Prior to Final Inspectn
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2008 |
INSP - FULL |
|
Prior to Final Inspectn |
NOTE: THE DOOR TO THE EXIT CORRIDOR WAS MARKED "NOT AN EXIT" AND IS NOW USED AS A STORAGE AREA. EXIT SIGNS WERE INSTALLED TO DIRECT EXITING THROUGH THE REAR STOCK ROOM AREA TO THE REAR EXIT. |
| 07/31/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRCTED.07/31/08 |
| 06/18/2008 |
INSP - FULL |
|
Violation |
1.) TFC 505.1 THE FRONT OF YOUR BUSINESS MUST BE ADDRESSED IN COMPLIANCE WITH PIMA COUNTY ADDRESSING REQUIREMENTS. |
| 06/18/2008 |
INSP - FULL |
|
Violation |
2.) TFC 1003.6 THE MARKED REAR EXIT ACCESS DOOR CANNOT BE OBSTRUCTED. THE MERCHANDISE OBSTRUCTING THE REAR EXIT ASSESS DOOR MUST BE REMOVED. |
| 06/18/2008 |
INSP - FULL |
|
Violation |
3.) TFC 1003.6 THE EXIT CORRIDOR LEADING TO THE REAR EXIT DOOR CANNOT BE OBSTRUCTED. THE STORAGE IN THE EXIT CORRIDOR MUST BE REMOVED. |
| 06/18/2008 |
INSP - FULL |
|
Violation |
4.) TFC 605.5 THE EXTENSION CORD USED TO POWER THE REFRIGERATOR IN THE BREAK ROOM IS NOT ALLOWED TO BE A SUBSTITUTE FOR PERMANENT WIRING AND MUST BE REMOVED. |
| 06/18/2008 |
INSP - FULL |
|
Violation |
5.) TFC 605.6 THE ELECTRICAL WIRING JUNCTION BOX IN THE CEILING ABOVE THE REAR DOOR MUST HAVE A COVER PLATE INSTALLED. |
| 06/18/2008 |
INSP - FULL |
|
Violation |
6.) TFC 703.1 THE HOLE IN THE SHEETROCK IN THE CEILING OF THE BACK ROOM NEEDS TO BE COVERED OR REPAIRED TO MAINTAIN THE REQUIRED FIRE RESISTANCE RATING. |
| 06/18/2008 |
INSP - FULL |
|
Violation |
7.) TFC 703.1.1 THE BROKEN CEILING TILE IN THE BACK ROOM NEEDS TO BE REPALCED TO MAINTAIN THE REQUIRED DRAFTSTOPPING AND FIREBLOCKING. |
| 06/18/2008 |
INSP - FULL |
|
Violation |
8.) TFC 906.2 ALL PORTABLE FIRE EXTINGUISHERS IN THE BUSINESS ARE PAST DUE FOR THEIR ANNUAL INSPECTION. THESE FIRE EXTINGUISHERS MUST BE INSPECTED AND PROPERLY TAGGED. |