Case: T08FR01589

Parcel: 133180080


Addresses:

1057 N KOLB RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/04/2009 INSP - FULL Approved
06/17/2008 INSP - FULL Correction Required 901.6 Maintenance of fire protection systems
1) Control valves at the sprinkler riser shall be signed
2) A spare head box with spare heads and a wrench shall be provided
3) open office space two heads are 36" apart, relocate one to provide proper coverage for the area
4) Center x-ray station requires sprinkler protection to be added
5)_ supply guage at the riser is inoperable, replace
6) Repair alarm trim valve
7) Provide a lock and chain for the riser control valve
8) The water motor gong is inoperable and needs to be repaired