Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01589
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/04/2009 | INSP - FULL | Approved | ||
06/17/2008 | INSP - FULL | Correction Required | 901.6 Maintenance of fire protection systems 1) Control valves at the sprinkler riser shall be signed 2) A spare head box with spare heads and a wrench shall be provided 3) open office space two heads are 36" apart, relocate one to provide proper coverage for the area 4) Center x-ray station requires sprinkler protection to be added 5)_ supply guage at the riser is inoperable, replace 6) Repair alarm trim valve 7) Provide a lock and chain for the riser control valve 8) The water motor gong is inoperable and needs to be repaired |