Case: T08FR01535

Parcel: 12702231G


Addresses:

5114 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/15/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/15/08
06/16/2008 INSP - FULL Violation 1.) TFC 605.5 EXTENSION CORDS SHALL NOT BE A SUBSTITUTE FOR PERMANENT WIRING. THE EXTENSION CORD USED TO POWER THE MICRO WAVE NEEDS TO BE REPLACED WITH AN APPROVED UL LISTED POWER STRIP.
06/16/2008 INSP - FULL Violation 2.) TFC 609.1 THE GREASE FILTER PANEL ABOVE THE DEEP FRYER NEEDS TO BE REPAIRED SO THAT IS SITS IN PLACE WHEN THE VENT FAN IS ON.
06/16/2008 INSP - FULL Violation 3.) TFC 3003.5.3 THE CO2 BOTTLES NEED TO BE SECURED TO PREVENT FALLING CAUSED BY CONTACT, VIBRATION OR SEISMIC ACTIVIVTY.
06/16/2008 INSP - FULL Violation 4.) TFC 1011.1 THE EXIT SIGN OVER THE REAR DOOR OF DINING AREA NEEDS TO BE REPAIRED OR REPLACED SO IT IS PROPERLY MARKED AS AN EXIT.
06/16/2008 INSP - FULL Violation 5.) TFC 1008.1.9 THE REAR EXIT DOOR FOR THE DINING AREA IS HARD TO OPEN. SERVICE THIS DOOR AND PANIC HARDWARE SO THAT IT OPENS WITH 15 POUNDS OF FORCE OR LESS.
06/16/2008 INSP - FULL Violation 6.) TFC 1008.1.9 THE DOUBLE DEAD BOLT LOCK ON THE REAR EXIT DOOR IS NOT PERMITTED BY THE FIRE CODE AND MUST BE REMOVED.
06/16/2008 INSP - FULL Violation 7.) TFC 605.4 THE MULTI-PLUG ADAPTER ABOVE THE FRONT EXIT DOOR USED FOR PLUGGING IN AVERTISEMENT SIGNS MUST BE REMOVED.
06/16/2008 INSP - FULL Violation 8.) TFC 1011.4 THE INTERNALLY ILLUMINATED EXIT SIGN ABOVE THE MAIN EXIT DOOR NEEDS TO BE REPAIRED SO IT IS ILLUMINATED AT ALL TIMES.