Case: T08FR01525

Parcel: 12213023A


Addresses:

4151 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/14/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/14/08
06/13/2008 INSP - FULL Violation 1.) TFC 1008.1.8 THE ROLLING CHAIN LINK GATE USED TO ENCLOSE THE REAR ROOL UP DOOR NEEDS TO HAVE A DOOR INSTALLED TO ALIGN WITH THE REAR EXIT DOOR TO ALLOW FOR UNOBSTRUCTED EXIT ACCESS.
06/13/2008 INSP - FULL Violation 2.) TFC 1008.1.8 THE CHAIN LINK GATE OUTSIDE OF THE EXIT DOOR IN THE NORTH WEST CORNER OF THE MAIN DISPLAY FLOOR NEEDS TO HAVE AN APPROVED LOCKING DEVICE THAT ALLOWS FOR EXIT ACCESS FROM THE EGRESS SIDE WITHOUT THE USE OF KEY OR SPECIAL KNOWLEDGE OR EFFORT.
06/13/2008 INSP - FULL Violation 3.) TFC 1008.1.4 THE SLIDE BOLT LATCHES ON THE FRONT EXIT DOOR ARE NOT PERMITTED BY THE FIRE CODE.
06/13/2008 INSP - FULL Violation 4.) TFC 1011.2 A.) THE EXIT SIGN OVER THE FRONT DOOR MUST BE INTERNALLY OR EXTERNALLY ILLUMINATED.
B.) THE EXIT SIGN OVER THE EXIT DOOR IN THE NORTHWEST CORNER OF THE MAIN DISPLAY FLOOR NEEDS TO BE INTERNALLY OR EXTERNALLY ILLUMINATED.
06/13/2008 INSP - FULL Violation 5.) TFC 1011.1 A DIRECTIONAL EXIT SIGN IS NEEDED ABOVE THE MAIN PATHWAY INDICATING THE DIRECTION TO EXIT IN THE NORTHWEST CORNER OF THE MAIN DISPLAY FLOOR.
06/13/2008 INSP - FULL Violation 6.) TFC 1504.3.2.2 THE INTERIOR SURFACE OF SPRAY BOOTH SHALL BE SMOOTH. THE SURFACES OF THE SPRAY BOOTH MSUT BE SCRAPED CLEAN OR THE SHEETROCK REMOVED AND REPLACED WITH CLEAN, SMOOTH SURFACE TO REMOVE BUILD-UP OF FLAMMABLE OVERSPRAY.
06/13/2008 INSP - FULL Violation 7.) TFC 1504.7.6 THE TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO THE ATMOSPHERE SHALL NOT BE LESS THAN 3 FEET FROM EXTERIOR WALLS AND ROOFS AND 10 FEET FROM OPENINGS INTO THE BUILDING. THE WOODEN BAFFLE COVERING THE EXHAUST FAN MUST BE REMOVED AND OVERSPRAY ACCUMULATED ON THE EXTERIOR WALL MSUT BE REMOVED.