Case: T08FR01522

Parcel: 12414038A


Addresses:

620 S CHERRY AV

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/17/2008 INSP - FULL Approved approved. Stock reduced
06/12/2008 INSP - FULL Violation Currently there is an excessive amount of pallets stored to close to property lines on the above lot.

The following fire code requirements shall be met:

These idle (combustible) pallets shall be stored in stacks NOT to exceed 10 feet in height 315.3.1.IFC

The structural stability and integrity of the stacks of pallets shall be maintained at all times. IFC 110.1.

Stacks of pallets shall NOT be stored within 10 feet of property or lot lines. IFC 315.3. This shall be strictly enforced.

Pallets shall NOT be stored within 10 feet from buildings.
IFC 314

All weeds on the all property shall be cut and removed. IFC 304.1.1

20 feet aisles must be maintained all times.