Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2009 | INSP - FULL | Approved | ||
| 06/11/2008 | INSP - FULL | Correction Required | 1) hydraulic calc plat shall be fixed to the riser 2) The spool piece below the riser shows rusting and pitting and shall be changed out 3) The sparehead box requires 2 additional horizontal 1/2" sidewall sprinklers 4) The lower guage at the riser is inoperable and shall be changed out 5) The main control valve at the riser is required to be secured with a lock and chain or electronicaly supervised 6) The combustable canopy attached to the rear of the building is required to have sprinkler protection. Submittals and permits are required. Submittals shall be made with in 30 days and work completed with in 60 days |